Performance Data Sheet
HGA5512EXD
General Information
Model HGA5512EXD Refrigerant R-22
Test Condition ASHRAE Performance Test Voltage 230V ~ 60HZ
Return Gas 18.3°C (65°F) RETURN GAS Motor Type PSC
Performance Information
Condensing Temperature (°F)
Evap Temp (°F)
80 90 100 110 120 130 140
Btu/h 3960 3660
Watts 582 606
Amps 2.78 2.94
-15
Lb/h 51.1 49.3
Btu/h 4570 4280 3950
Watts 598 627 663
Amps 2.84 3.02 3.19
-10
Lb/h 58.7 57.1 55.1
Btu/h 5210 4920 4590 4220
Watts 613 646 686 732
Amps 2.89 3.09 3.28 3.47
-5
Lb/h 66.4 65.2 63.4 61.2
Btu/h 5880 5590 5250 4880 4470
Watts 625 662 707 757 812
Amps 2.94 3.15 3.37 3.58 3.80
0
Lb/h 74.5 73.5 71.9 69.8 67.3
Btu/h 6600 6290 5940 5550 5130
Watts 635 677 725 780 840
Amps 2.98 3.21 3.45 3.68 3.92
5
Lb/h 83.0 82.1 80.7 78.8 76.3
Btu/h 7360 7040 6670 6260 5820 5350 4860
Watts 642 688 742 801 865 932 1000
Amps 3.01 3.27 3.52 3.78 4.04 4.31 4.59
10
Lb/h 92.0 91.2 89.9 88.1 85.7 82.9 79.5
Btu/h 8180 7830 7440 7010 6540 6040 5520
Watts 646 698 756 820 888 960 1030
Amps 3.03 3.31 3.58 3.86 4.15 4.44 4.75
15
Lb/h 102 101 99.7 97.9 95.6 92.7 89.4
Btu/h 9060 8690 8270 7810 7310 6770 6220
Watts 648 705 768 836 909 985 1060
Amps 3.05 3.34 3.64 3.94 4.25 4.57 4.90
20
Lb/h 112 111 110 108 106 103 99.7
Page view 0
1 2

Summary of Contents

Page 1 - Performance Data Sheet

Performance Data SheetHGA5512EXDGeneral InformationModel HGA5512EXD Refrigerant R-22Test Condition ASHRAE Performance Test Voltage 230V ~ 60HZReturn G

Page 2 - Tc = Condensing Temperature

Btu/h 10000 9620 9160 8660 8120 7550 6960Watts 646 708 777 850 927 1010 1090Amps 3.05 3.36 3.68 4.00 4.34 4.68 5.0425Lb/h 123 122 121 119 117 114 111B

Comments to this Manuals

No comments